| Technical Data - Air Cooled Screw Chiller - Two Circuits - R134a - Non Tropical | |||||||||||||||||||||||||||
| Model | Tac1s2L100 | Tac1s2L120 | Tac1s2L140 | Tac1s2L160 | Tac1s2L180 | Tac1s2L220 | Tac1s2L250 | Tac1s2L280 | Tac1s2L320 | Tac1s2L360 | |||||||||||||||||
| General | actual unit capacity | RT | 64.7 | 76.6 | 89.4 | 108 | 122.3 | 146.8 | 163.3 | 184.3 | 217.9 | 250.3 | |||||||||||||||
| kW | 227.6 | 269.3 | 314.2 | 379.9 | 430 | 516.2 | 574.2 | 648 | 766.1 | 880.2 | |||||||||||||||||
| COP | 3.66 | 3.81 | 3.98 | 3.94 | 3.83 | 4.18 | 4.19 | 4.06 | 4.1 | 4.08 | |||||||||||||||||
| Number of independent refrigerant circuits | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||||||||||||||||
| oil charge (each cycle) flow control | l | 15 | 15 | 15 | 22 | 22 | 22 | 19 | 19 | 30 | 30 | ||||||||||||||||
| electrical data | Power Supply | 380 v / 3PH / 50Hz | |||||||||||||||||||||||||
| total power Input | kW | 73.84 | 82.24 | 90.54 | 11.92 | 127.72 | 146.88 | 160.28 | 182.88 | 218.04 | 247.04 | ||||||||||||||||
| compressor (each cycle) | compressor type | compact screw | |||||||||||||||||||||||||
| quantity | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||||||||||||||||
| Power Input | kW | 31.1 | 35.3 | 39.5 | 48.2 | 56.1 | 61.8 | 68.5 | 79.8 | 93.5 | 108 | ||||||||||||||||
| rated current | A | 53.7 | 62.1 | 68.8 | 76.5 | 91.6 | 106.8 | 120 | 136.5 | 155.2 | 174.8 | ||||||||||||||||
| locked rotor ampere | A | 206 | 267 | 290 | 394 | 439 | 520 | 612 | 665 | 436 | 465 | ||||||||||||||||
| max operating current | A | 79 | 98 | 124 | 144 | 155 | 182 | 196 | 214 | 280 | 310 | ||||||||||||||||
| condenser | condenser type | v | w | w | w | w | w | w | w | w | w | ||||||||||||||||
| number of coils | 2 | 4 | 4 | 4 | 4 | 8 | 8 | 8 | 8 | 8 | |||||||||||||||||
| Fans | number | 6 | 6 | 6 | 8 | 8 | 12 | 12 | 12 | 16 | 16 | ||||||||||||||||
| max operating current | A | 3.9 | 3.9 | 3.9 | 3.9 | 3.9 | 3.9 | 3.9 | 3.9 | 3.9 | 3.9 | ||||||||||||||||
| Power Input | kW | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | 1.94 | ||||||||||||||||
| total Power inputs include compressors and condenser fans power input | |||||||||||||||||||||||||||
| All design data and specification are generated in below conditions: | |||||||||||||||||||||||||||
| _ Evaporator inlet / outlet chilled water temperature: 55/44 °F | |||||||||||||||||||||||||||
| _ Fouling factor of water in evaporator is considered 0.000044 m2.K/W | |||||||||||||||||||||||||||
| _ Ambient temperature: 33 °C (95 °F) | |||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||